Grid-forming inverter to stabilize microgrids

Toshiba is rolling out a good synchronous inverter that stabilizes power fluctuations in microgrids. JAPAN company said it has tested these devices in conjunction with PV and battery storage.

Toshiba is rolling out a grid-forming (GFM) inverter for applications in microgrids.

JAPAN industrial group said the brand new inverter can keep up with the grid frequency of distribution systems by giving pseudo-inertia through power output from the inverter once the grid frequency rapidly fluctuates.

Toshiba has implemented a control algorithm of the grid-forming inverter in battery energy storage systems rather than conventional control algorithm without inertia, so when you can find rapid fluctuations in renewable energy output or power demands, the inverter outputs power and generates a synthetic inertia to keep up the grid frequency, the business said in a statement. This instantly suppresses sudden drops in frequency, realizing a well balanced power.

Toshiba tested the inverter in a simulated microgrid with a grid frequency of 50 Hz, a 40% renewable energy rate, and five 20 kW/14.9 kWh batteries. The machine also featured a diesel synchronous generator with a capacity of 125 kVA, and two load banks to alter the energy load.

It had been demonstrated that under load fluctuations of 50 kW, grid frequency reductions were suppressed by 70%, from 2.4 Hz (50.0 to 47.6 Hz) to 0.6 Hz (50.0 Hz to 49.4 Hz), the business said, in mention of the test outcomes. The frequency threshold for power interruptions because of grid frequency fluctuations in East Japan is defined at 48.5 Hz, and verifications using actual equipment ensured that the frequency didn’t fall below this threshold, demonstrating the realization of a well balanced power that avoids power outages.

The business conducted another test on a 20 kW PV system without batteries, and discovered that the grid frequency was suppressed by approximately 30%, from 1 Hz (50.0 to 49.0 Hz) to 0.7 Hz (50.0 to 49.3 Hz).

Toshiba also verified that instantaneous load on the GFM inverter could be reduced by 30%, from 22 to 16 kW, by selecting an inertia ideal for parallel operation of synchronous generators with internal combustion engines, like those likely to be utilized in a microgrid, it said.

The business said it plans to reveal the outcomes at the Annual Conference of the energy and Energy Society of the Institute of Electrical Engineers of Japan in September. It will discuss its findings at the 2022 IEEE Energy Conversion Congress and Exposition (ECCE2022) in October.